Paper-wrapped winding wire is a special type of conductor widely used in electrical equipment such as power transformers and motors.
Its basic structure involves wrapping a layer or multiple layers of insulating paper around a conductive metal wire (usually copper or aluminum) to enhance the wire's electrical insulation and thermal properties.
Recommended conductor sizes:
Sizes for flat conductors:
Thickness 0.80-12.00mm
Width 3.00-25.00mm
Width-thickness ratio ≤20
Sizes for round conductors:
Diameter 2.00-5.00mm
Conductor Materials:
•High-quality oxygen-free copper rods with an oxygen content of less than 20ppm. The conductivity exceeds 100% after annealing.
•High-quality aluminum electrical rods, with a conductivity exceeding 62% after annealing
Winding insulation materials:
• Power cable paper
• High elongation fiber paper
• High density insulation paper
• Aromatic polyamide paper (Nomex)
• Heat-resistant insulation paper
• PET film
Users can specify the brand, model, and specifications of insulation material
Paper Covered Round Wire Insulation Thickness | |||||||||||||
Standard Insulation Thickness(mm) |
0.3 | 0.45 | 0.80 | 1.20 | 1.80 | 4.25 | |||||||
Tolerance(mm) | ±0.05 | ±0.05 | ±0.10 | ±0.12 | ±0.15 | ±0.30 |
Paper Covered Flat Wire Insulation Thickness | ||||||||
Standard Insulation Thickness(mm) |
0.45 | 0.60 | 0.95 | 1.35 | 1.60 | 1.95 | 2.45 | 2.95 |
Maximum Insulation Thickness(A-a) |
0.57 | 0.74 | 1.14 | 1.56 | 1.84 | 2.23 | 2.77 | 3.32 |
Minimum Insulation Thickness(B-b) |
0.40 | 0.53 | 0.85 | 1.20 | 1.45 | 1.80 | 2.30 | 2.75 |